DG275-2 (3 phase)

Electric Power
Electric Power (355)

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Engine
  • Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight
Generator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
Cat EMCP Control Panel
The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further...
Design Criteria
  • The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
  • Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water
UL 2200 / CSA - Optional
  • UL 2200 listed packages
  • CSA Certified
  • Certain restrictions may apply.
  • Consult with your Cat® Dealer.
Worldwide Product Support
Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries.
Engine
  • Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight
Generator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
Cat EMCP Control Panel
The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.
Design Criteria
  • The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
  • Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water
UL 2200 / CSA - Optional
  • UL 2200 listed packages
  • CSA Certified
  • Certain restrictions may apply.
  • Consult with your Cat® Dealer.
Worldwide Product Support
Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries.

Generator Set Specifications

Voltage
120 / 208, 120 / 240, 277 / 480, 346 / 600 VAC
Frequency
60 Hz
Natural Gas Rating
275 eKW
Speed
1800 rpm
Emissions/Fuel Strategy
U.S. EPA Certified for Non-Emergency Application
Displacement
864.71in³

Engine Specifications

Engine Model
14.2 L Spark - Ignited
Fuel Type
Natural Gas
Fuel System
Carburetor, Down Draft
Compression Ratio
9.5:1
Bore
5.31in
Stroke
6.5in

Generator Set Dimensions

Length
136in
Width
57.6in
Height
66.1in
Weight
6274lb

Standard/Optional Features

Standard Equipment:

  • Cooling
    • Factory-installed radiator
    • 50/50 Ethylene glycol antifreeze
    • Closed coolant recovery system
    • Standard ambient temperatures up to 50°C (122°F)
    • Radiator and cooling fan complete with protective guards
  • Air Inlet
    • Single element air filter
  • Fuel
    • Primary and secondary fuel shut-off
    • Low fuel pressure switch
    • Fuel pressure test po
    • Dual lock off valves
    • NPT connection
    • Natural Gas or LP Vapor
  • Generator
    • Class H insulation material
    • Permanent magnet excitation
    • Full load capacity alternator
    • Permanent magnet excitation
    • Integrated Voltage Regulator
    • Class H insulation material
    • Full load capacity alternator
    • IP23 Protection
    • Matched to the performance and output characteristics of Cat engines
  • Exhaust
    • Exhaust outlet with 3” pipe
  • Controls
    • EMCP 4.2 Series generator set controller
  • Mounting
    • Vibration isolaton (puck type)
    • Rubber vibration isolators
  • Electric Starting And/or Prelube
    • Solenoid activated starter motor
    • Engine electrical system
    • Battery cables
    • Solenoid activated starter motor
  • Electric Power - Package Serial Number Prefix
    • Battery charging alternator
  • Governor
    • Electronic governor (non adjustable)
  • Control Panel
    • EMCP 4.2 Series generator set controller
  • Starting/charging
    • Batteries with rack and cables
    • 12 volt starting motor

Optional Equipment:

  • Starting/charging
    • Charging alternator
    • Jacket water heater
    • Battery heater
    • Battery charger – UL Listed 10 amp
  • General
    • Suitable for Use as Service Equipment (SUSE)
    • CSA Certification
    • Enclosures: sound attenuated, weather protective
    • Automatic transfer switches (ATS)
    • UL 2200 package
  • Generator
    • Anti-condensation heater
    • Shunt trip and auxiliary contact breaker
    • Thermal magnetic or electronic trip MCCBs
    • Excitation: [ ] Permanent Magnet Excited (PM)
    • Anti-condensation heater
    • Oversize and premium generators

Take The Virtual Product Tour To Explore The Features And Benefits of the DG275-2 (3 phase)

See how DG275 GC (3 phase) compares against frequently compared products

DG275 GC (3 phase) Electric Power

Selected Model

Electric Power

View Full Specs

Electric Power

View Full Specs

Compare with other Cat Models

Compare Now

Media Gallery

Check out our current offers

View Specials
Translate »