3516B (60 Hz) with Upgradeable Package

Diesel Generator Sets
Diesel Generator Sets (172)

Overview

The3516B with the upgradeable packaging design has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance to matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
EMCP 4 Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirements
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Single-Source Supplier
  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
EMCP 4 Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirements
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Single-Source Supplier
  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Generator Set Specifications

Minimum Rating
1640 ekW
Maximum Rating
2250 ekW
Emissions/Fuel Strategy
Low fuel, Low Emissions
Voltage
380 to 480 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Standby Rating
2250 ekW
Prime Power Rating
1825 ekW

Engine Specifications

Engine Model
3516B TA, V-16, 4-Stroke Water-Cooled Diesel
Bore
6.69in
Stroke
7.48in
Displacement
4210.64in
Compression Ratio
14.0:1
Aspiration
TA
Fuel System
MEUI
Governor Type
ADEM™ A4

Generator Set Dimensions

Length - Maximum
234.5in
Width - Maximum
90in
Height - Maximum
98.2in
Dry Weight - Genset (maximum)
30310lb

Standard/Optional Features

Standard Equipment:

  • Air Inlet System
    • Air cleaner; single element canister type
  • Control Panels
    • PLC functionality
    • Oil pressure (psi, kPa or bar)
    • Text alarm/event descriptions
    • KVAR/PF modes
    • Cat connect
    • Overspeed
    • Amps (per phase & average)
    • Programmable protective relaying functions:
    • DC volts
    • EMCP 4.2B
    • Power factor (per phase & average)
    • Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
    • Load histogram feature
    • Generator set packages include:
    • Frequency (Hz)
    • Emergency stop pushbutton
    • Over/under voltage (27/59)
    • RFI suppression
    • 24 Volt DC operation
    • Low coolant level
    • Reverse power (kW) (32) - Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
    • 4 Programmable relay outputs (Form A)
    • Volts (L-L & L-N)
    • Caterpillar's voltage regulator
    • IVR includes:
    • Auto/start/stop control
    • kVA (per phase, average & percent)
    • Lamp test
    • Over/under frequency (81 o/u)
    • Environmental sealed front face
    • 3 Phase voltage sensing
    • Engine cool
    • kVAr-hr (total)
    • Low oil pressure
    • Accessory module data link
    • Emergency stop
    • Customer data link (Modbus RTU)
    • Communications:
    • Warning/shutdown with common LED indication of shutdowns for:
    • 0 True RMS AC metering, 3-phase, +/-2% accuracy
    • Digital indication for:
    • Customizable screens
    • Failure to start (overcrank)
    • Serial annunciator module data link
    • Coolant temperature
    • Controls:
    • Overcurrent (50/51)
    • Number of I/O varies on options selected
    • Reactive droop capability
    • Low coolant temperature
    • High coolant temperature
    • Min / max exciter
    • Alarm acknowledge
    • RPM
    • Generator phase sequence
    • Limiter and exciter diode monitor
    • Speed adjust
    • Operating hours
    • kW (per phase, average & percent)
    • 3 Analog inputs
    • Generator mounted - rear facing
    • 6 Customer programmable digital inputs
  • Lubrication System
    • Oil filter, filler and dipstick
    • Oil drain lines and valve
    • Gear type lube oil pump
    • Fumes disposal
    • Lubricating oil
  • Mounting System
    • Rubber anti-vibration mounts - shipped loose
    • Rails - engine/generator/radiator mounting
    • Anti-vibration mounts (shipped loose)
  • Starting System
    • 45 Amp Charging alternator
    • 24 Volt electric starting motor
    • Battery and battery rack w/cables
    • Battery disconnect switch
  • Literature
    • Parts book
    • Operation & Maintenance Manual

Optional Equipment:

  • Control System
    • EMCP 4.3, EMCP 4.4
  • Air Inlet System
    • Dual element air cleaner
    • Single element filter
  • Cooling System
    • Water level switch gauges
    • Optional installed ATAAC radiators
    • Standard ambient ATAAC radiators
    • Standard ambient radiators
    • Coolant
    • Optional installed radiators
  • Crankcase System
    • Explosion relief valves
    • No explosion relief valves
    • Ventilation system
  • Exhaust System
    • Elbows
    • Flange and exhaust expanders
    • Tier 4 clean emissions module
    • Tier 4 clean emission MOD Kits
    • Clean emission parts
    • Exhaust offset
    • Mufflers
    • Tier 4 dosing cabinet
    • Flanges
    • Flexible fittings
    • Y Adapters
  • Fuel System
    • Fuel priming pumps (Tier 4) - Manual or electric
    • Primary fuel filter
  • General
    • US aid emblem
    • Special paint (Colors other than Caterpillar yellow or high performance paints)
  • Generators And Attachments
    • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
    • Generator conversion
    • Differential current transformers (DCT)
    • Differential current transformers (DCT) 8.7 kV and 15 kV classes
    • Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
    • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
    • Thermostat for space heater
    • Space heater
    • High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
    • Alternator air cleaner
    • High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
    • Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
  • Instrumentation
    • Pyrometer and Thermocouples
  • Lubrication System
    • Oil level regulator
    • Prelube pumps
    • Lube oil in standard sump
  • Mounting System
    • Puck style low efficiency isolators
    • Spring type vibration isolators
    • IBC vibration isolators
  • Power Connections
    • Right side power connections
    • Ground cables between generator and terminal box
    • Neutral ground connections
    • Low voltage Circuit breakers
    • 2700 Frame, four lead, four terminal
    • Rear power connections
    • Left side power connections
    • Center post busbars
  • Special Tests / Reports
    • PGS Test report @ 0.8 power factor
    • PGS Test report @ 1.0 power factor
    • Fuel consumption test
    • Canadian Standards Association certification
    • Torsional vibration analysis reports
    • IBC Certification
    • Generator test report
    • Generator set fuel consumption test
    • OSHPD Certification
    • Standard engine test charge
  • Starting And Charging
    • Engine barring device
    • Air pressure regulator
    • Starter cover
    • Electric starting motors
    • Jacket water heaters
    • Air starting motors
    • 24 Volt battery set - Dry
    • 10, 20, 35 and 50 Amp Battery chargers
  • Extended Service Coverage
    • Platinum, Gold and Silver coverage

Take The Virtual Product Tour To Explore The Features And Benefits of the 3516B (60 Hz) with Upgradeable Package

See how 3516B (60 Hz) with Upgradeable Package compares against frequently compared products

3516B (60 Hz) with Upgradeable Package Diesel Generator Sets

Engine Model
3516B TA, V-16, 4-Stroke Water-Cooled Diesel
Voltage
380 to 480 Volts
Maximum Rating
2250 ekW
Selected Model

C1.1 (60 Hz) Diesel Generator Sets

Engine Model
C1.1, In-line 4, 4-cycle diesel
Voltage
110 to 480 Volts
Maximum Rating
8.8 ekW
View Full Specs

C1.1 (50 Hz) Diesel Generator Sets

Engine Model
C1.1, In-line 4 4-cycle diesel
Voltage
110 to 415 Volts
Maximum Rating
9.5 kVA
View Full Specs

Compare with other Cat Models

Compare Now

Media Gallery

Check out our current offers

View Specials
Translate »